NR 665.1035(3)(j)5.a.a. The owner or operator may develop a written procedure that identifies the conditions that justify a delay of repair. In those cases, reasons for delay of repair may be documented by citing the relevant sections of the written procedure.
NR 665.1035(3)(j)5.b.b. If delay of repair was caused by depletion of stocked parts, there shall be documentation that the spare parts were sufficiently stocked on-site before depletion and the reason for depletion.
NR 665.1035(4)(4)Maintain records of the monitoring, operating and inspection information required by sub. (3) (c) to (j) for at least 3 years following the date of each occurrence, measurement, maintenance, corrective action or record.
NR 665.1035(5)(5)For a control device other than a thermal vapor incinerator, catalytic vapor incinerator, flare, boiler, process heater, condenser or carbon adsorption system, record monitoring and inspection information indicating proper operation and maintenance of the control device in the facility operating record.
NR 665.1035(6)(6)Record up-to-date information and data used to determine whether or not a process vent is subject to s. NR 665.1032, including supporting documentation required by s. NR 665.1034 (4) (b) when application of the knowledge of the nature of the hazardous waste stream or the process by which it was produced is used, in a log that is kept in the facility operating record.
NR 665.1035 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
subch. BB of ch. NR 665Subchapter BB — Air Emission Standards for Equipment Leaks
NR 665.1050NR 665.1050Applicability.
NR 665.1050(1)(1)This subchapter applies to owners and operators of facilities that treat, store or dispose of hazardous wastes (except as provided in s. NR 665.0001).
NR 665.1050(2)(2)Except as provided in s. NR 665.1064 (11), this subchapter applies to equipment that contains or contacts hazardous wastes with organic concentrations of at least 10 percent by weight that are managed in one of the following:
NR 665.1050(2)(a)(a) A unit that is subject to the licensing requirements of ch. NR 670.
NR 665.1050(2)(b)(b) A unit (including a hazardous waste recycling unit) that is not exempt from licensing under s. NR 662.017 (i.e., a hazardous waste recycling unit that is not a “90-day” tank or container) and that is located at a hazardous waste management facility otherwise subject to the licensing requirements of ch. NR 670.
NR 665.1050(2)(c)(c) A unit that is exempt from licensing under s. NR 662.017 (i.e., a “90-day” tank or container) and is not a recycling unit under s. NR 661.0006.
NR 665.1050(3)(3)Each piece of equipment to which this subchapter applies shall be marked in such a manner that it can be distinguished readily from other pieces of equipment.
NR 665.1050(4)(4)Equipment that is in vacuum service is excluded from ss. NR 665.1052 to 665.1060 if it is identified as required in s. NR 665.1064 (7) (e).
NR 665.1050(5)(5)Equipment that contains or contacts hazardous waste with an organic concentration of at least 10 percent by weight for less than 300 hours per calendar year is excluded from ss. NR 665.1052 to 665.1060 if it is identified, as required in s. NR 665.1064 (7) (f).
NR 665.1050(7)(7)Purged coatings and solvents from surface coating operations subject to the national emission standards for hazardous air pollutants (NESHAP) for the surface coating of automobiles and light-duty trucks at 40 CFR part 63, subpart IIII, are not subject to the requirements of this subchapter.
NR 665.1050 NoteNote: Sections NR 665.1052 to 665.1064 apply to equipment associated with hazardous waste recycling units previously exempt under s. NR 661.0006 (3) (a).  Other exemptions under ss. NR 661.0004 and 665.0001 (3) are not affected by these requirements.
NR 665.1050 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06; CR 16-007: cr. (7) Register July 2017 No. 739, eff. 8-1-17; CR 19-082: am. (2) (b), (c) Register August 2020 No. 776, eff. 9-1-20.
NR 665.1051NR 665.1051Definitions. As used in this subchapter, all terms shall have the meaning given them in s. NR 664.1031, ch. 291, Stats., and chs. NR 660 to 666.
NR 665.1051 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
NR 665.1052NR 665.1052Standards: pumps in light liquid service.
NR 665.1052(1)(a)(a) Monitor each pump in light liquid service monthly to detect leaks by the methods specified in s. NR 665.1063 (2), except as provided in subs. (4) to (6).
NR 665.1052(1)(b)(b) Check each pump in light liquid service by visual inspection each calendar week for indications of liquids dripping from the pump seal.
NR 665.1052(2)(a)(a) If an instrument reading of 10,000 ppm or greater is measured, a leak is detected.
NR 665.1052(2)(b)(b) If there are indications of liquids dripping from the pump seal, a leak is detected.
NR 665.1052(3)(a)(a) When a leak is detected, repair it as soon as practicable, but not later than 15 calendar days after it is detected, except as provided in s. NR 665.1059.
NR 665.1052(3)(b)(b) Make a first attempt at repair (e.g., tightening the packing gland) no later than 5 calendar days after each leak is detected.
NR 665.1052(4)(4)Each pump equipped with a dual mechanical seal system that includes a barrier fluid system is exempt from sub. (1), provided all of the following requirements are met:
NR 665.1052(4)(a)(a) Each dual mechanical seal system shall be one of the following:
NR 665.1052(4)(a)1.1. Operated with the barrier fluid at a pressure that is at all times greater than the pump stuffing box pressure.
NR 665.1052(4)(a)2.2. Equipped with a barrier fluid degassing reservoir that is connected by a closed-vent system to a control device that complies with s. NR 665.1060.
NR 665.1052(4)(a)3.3. Equipped with a system that purges the barrier fluid into a hazardous waste stream with no detectable emissions to the atmosphere.
NR 665.1052(4)(b)(b) The barrier fluid system may not be a hazardous waste with organic concentrations 10 percent or greater by weight.
NR 665.1052(4)(c)(c) Equip each barrier fluid system with a sensor that will detect failure of the seal system, the barrier fluid system or both.
NR 665.1052(4)(d)(d) Check each pump by visual inspection, each calendar week, for indications of liquids dripping from the pump seals.
NR 665.1052(4)(e)1.1. Check each sensor described in par. (c) daily, or equip it with an audible alarm and check the alarm monthly to ensure it is functioning properly.
NR 665.1052(4)(e)2.2. Determine, based on design considerations and operating experience, a criterion that indicates failure of the seal system, the barrier fluid system or both.
NR 665.1052(4)(f)1.1. If there are indications of liquids dripping from the pump seal or the sensor indicates failure of the seal system, the barrier fluid system or both based on the criterion determined in par. (e) 2., a leak is detected.
NR 665.1052(4)(f)2.2. When a leak is detected, repair it as soon as practicable, but not later than 15 calendar days after it is detected, except as provided in s. NR 665.1059.
NR 665.1052(4)(f)3.3. Make a first attempt at repair (e.g., relapping the seal) no later than 5 calendar days after each leak is detected.
NR 665.1052(5)(5)Any pump that is designated, as described in s. NR 665.1064 (7) (b), for no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, is exempt from subs. (1), (3) and (4) if the pump meets all of the following requirements:
NR 665.1052(5)(a)(a) It has no externally actuated shaft penetrating the pump housing.
NR 665.1052(5)(b)(b) It operates with no detectable emissions as indicated by an instrument reading of less than 500 ppm above background measured by the methods specified in s. NR 665.1063 (3).
NR 665.1052(5)(c)(c) It is tested for compliance with par. (b) initially upon designation, annually and at other times requested by the department.
NR 665.1052(6)(6)If any pump is equipped with a closed-vent system capable of capturing and transporting any leakage from the seal or seals to a control device that complies with s. NR 665.1060, it is exempt from subs. (1) to (5).
NR 665.1052 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
NR 665.1053NR 665.1053Standards: compressors.
NR 665.1053(1)(1)Equip each compressor with a seal system that includes a barrier fluid system and that prevents leakage of total organic emissions to the atmosphere, except as provided in subs. (8) and (9).
NR 665.1053(2)(2)Each compressor seal system as required in sub. (1) shall be one of the following:
NR 665.1053(2)(a)(a) Operated with the barrier fluid at a pressure that is at all times greater than the compressor stuffing box pressure.
NR 665.1053(2)(b)(b) Equipped with a barrier fluid system that is connected by a closed-vent system to a control device that complies with s. NR 665.1060.
NR 665.1053(2)(c)(c) Equipped with a system that purges the barrier fluid into a hazardous waste stream with no detectable emissions to atmosphere.
NR 665.1053(3)(3)The barrier fluid may not be a hazardous waste with organic concentrations 10 percent or greater by weight.
NR 665.1053(4)(4)Equip each barrier fluid system described in subs. (1) to (3) with a sensor that will detect failure of the seal system, barrier fluid system or both.
NR 665.1053(5)(a)(a) Check each sensor required in sub. (4) daily, or equip it with an audible alarm and check the alarm monthly to ensure it is functioning properly, unless the compressor is located within the boundary of an unmanned plant site, in which case check the sensor daily.
NR 665.1053(5)(b)(b) Determine, based on design considerations and operating experience, a criterion that indicates failure of the seal system, the barrier fluid system or both.
NR 665.1053(6)(6)If the sensor indicates failure of the seal system, the barrier fluid system or both based on the criterion determined under sub. (5) (b), a leak is detected.
NR 665.1053(7)(a)(a) When a leak is detected, repair it as soon as practicable, but not later than 15 calendar days after it is detected, except as provided in s. NR 665.1059.
NR 665.1053(7)(b)(b) Make a first attempt at repair (e.g., tightening the packing gland) no later than 5 calendar days after each leak is detected.
NR 665.1053(8)(8)A compressor is exempt from subs. (1) and (2) if it is equipped with a closed-vent system capable of capturing and transporting any leakage from the seal to a control device that complies with s. NR 665.1060, except as provided in sub. (9).
NR 665.1053(9)(9)Any compressor that is designated, as described in s. NR 665.1064 (7) (b), for no detectable emission as indicated by an instrument reading of less than 500 ppm above background is exempt from subs. (1) to (8) if the compressor meets all of the following requirements:
NR 665.1053(9)(a)(a) It is determined to be operating with no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, measured by the method specified in s. NR 665.1063 (3).
NR 665.1053(9)(b)(b) It is tested for compliance with par. (a) initially upon designation, annually and at other times requested by the department.
NR 665.1053 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
NR 665.1054NR 665.1054Standards: pressure relief devices in gas or vapor service.
NR 665.1054(1)(1)Except during pressure releases, operate each pressure relief device in gas or vapor service with no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, measured by the method specified in s. NR 665.1063 (3).
NR 665.1054(2)(a)(a) After each pressure release, return the pressure relief device to a condition of no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, as soon as practicable, but no later than 5 calendar days after each pressure release, except as provided in s. NR 665.1059.
NR 665.1054(2)(b)(b) No later than 5 calendar days after the pressure release, monitor the pressure relief device to confirm the condition of no detectable emissions, as indicated by an instrument reading of less than 500 ppm above background, measured by the method specified in s. NR 665.1063 (3).
NR 665.1054(3)(3)Any pressure relief device that is equipped with a closed-vent system capable of capturing and transporting leakage from the pressure relief device to a control device described in s. NR 665.1060 is exempt from subs. (1) and (2).
NR 665.1054 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
NR 665.1055NR 665.1055Standards: sampling connection systems.
NR 665.1055(1)(1)Equip each sampling connection system with a closed-purge, closed-loop or closed-vent system. The system shall collect the sample purge for return to the process or for routing to the appropriate treatment system. Gases displaced during filling of the sample container are not required to be collected or captured.
NR 665.1055(2)(2)Each closed-purge, closed-loop or closed-vent system required in sub. (1) shall meet one of the following requirements:
NR 665.1055(2)(a)(a) It returns the purged process fluid directly to the process line.
NR 665.1055(2)(b)(b) It collects and recycles the purged process fluid.
NR 665.1055(2)(c)(c) It is designed and operated to capture and transport all the purged process fluid to a waste management unit that complies with the applicable requirements of ss. NR 665.1085 to 665.1087 or a control device that complies with s. NR 665.1060.
NR 665.1055(3)(3)In-situ sampling systems and sampling systems without purges are exempt from subs. (1) and (2).
NR 665.1055 HistoryHistory: CR 05-032: cr. Register July 2006 No. 607, eff. 8-1-06.
NR 665.1056NR 665.1056Standards: open-ended valves or lines.